Note on BH-10: Max inclination of 5.8° with 6.9 ft lateral departure at 479 ft TD exceeds the project tolerance threshold of 5°. Recommend engineer review to assess impact on borefield thermal resistance and adjacent bore clearance. All other bores are within design tolerances.
Trajectory Plots — Selected Bores
Plan View (N–E) · Designed vs. Actual Bottom-Hole Position
Plan view shows surface collar (centre) and TD position (endpoint). Design tolerance ring = 5.0 ft radius.
BH-06 · 463 ft · 1.5° · PASS
Actual path
Tolerance
BH-07 · 482 ft · 4.2° · WARN
Actual path
Tolerance
BH-10 · 479 ft · 5.8° · FLAG
Actual path
Tolerance
Per-Bore Survey Results
All 24 Bores — Deviation Summary
Bore ID
Depth (ft)
Max Inc (°)
Azimuth (°)
Lat. Dep. (ft)
TVD (ft)
Status
BH-01
459
1.2
045
1.3
459.0
PASS
BH-02
466
2.4
135
3.9
464.9
PASS
BH-03
476
1.8
210
2.6
475.4
PASS
BH-04
453
0.8
090
0.7
452.8
PASS
BH-05
469
3.8
315
10.2
468.1
WARN
BH-06
463
1.5
180
3.0
462.4
PASS
BH-07
482
4.2
060
17.4
480.6
WARN
BH-08
456
1.2
270
1.3
456.0
PASS
BH-09
472
2.0
150
3.3
472.1
PASS
BH-10
479
5.8
225
26.9
476.0
FLAG
BH-11
469
3.4
030
8.5
468.1
WARN
BH-12
459
1.6
105
2.3
459.3
PASS
BH-13
486
2.2
190
3.9
484.9
PASS
BH-14
476
1.0
075
1.0
475.7
PASS
BH-15
466
2.7
330
5.2
464.9
PASS
BH-16
492
1.4
260
2.0
492.1
PASS
BH-17
463
0.9
120
1.0
462.6
PASS
BH-18
469
2.1
045
3.6
468.8
PASS
BH-19
479
1.8
195
2.6
478.7
PASS
BH-20
459
2.9
285
5.9
458.7
PASS
BH-21
472
1.1
015
1.3
472.4
PASS
BH-22
466
2.4
165
4.3
464.9
PASS
BH-23
456
1.7
240
2.3
455.7
PASS
BH-24
476
0.6
090
0.3
475.7
PASS
Status thresholds: PASS <3.0° · WARN 3.0–5.0° · FLAG >5.0° · Lateral departure calculated at TD.
Synthetic Data Notice: This is a sample report generated for demonstration purposes. All bore IDs, survey results, project details, and numerical values are synthetic. They are representative of real networked geothermal project characteristics but do not correspond to any actual survey.